Sincro 3-Phase Supercompact 4-Pole Industrial Alternators for North America
0,00 €
Sincro Three-Phase Supercompact 4-Pole Alternators BRUSHLESS / AVR
CSA/UL Certified for North American Industrial Gen-Sets
The Sincro SK 160 series offers premium three-phase supercompact alternators engineered for peak performance in industrial applications. These 4-pole, synchronous low-voltage AC alternators operate at 1800 RPM and feature a reliable brushless design. Specifically tailored and CSA/UL certified for the North American market, they provide exceptional quality and safety. As a brand of Soga S.p.A., Sincro proudly manufactures these units in Europe under rigorous ISO 9001:2008 quality management systems.
Core Features & OEM Benefits
Space-Saving Design: Engineered via advanced FEM systems, these alternators boast a supercompact footprint that optimizes the electromagnetic circuit. This allows OEMs to significantly cut gen-set manufacturing costs (including canopies and basements) as well as logistics expenses like shipping and storage.
Simplified Installation: The terminal box layout is designed to allow cable exits from either side, easing connection procedures. Additionally, the protection grids utilize special hooks for fast assembly and disassembly.
Safe & Easy Maintenance: The analogic Automatic Voltage Regulator (AVR) can be safely accessed for tuning and setting operations through a dedicated small opening on the terminal box.
Rugged Durability: Every unit comes with standard tropicalization to ensure the windings and internal components withstand challenging environmental conditions.
Technical Specifications
Alternator Type: Synchronous low voltage AC alternator.
Phase: Three Phase.
Poles & Speed: 4 Poles, 1800 RPM.
Voltage Base: 480V at 60 Hz.
Excitation: Brushless.
Voltage Regulation: Analogic AVR powered by an auxiliary winding.
Winding Pitch: Full pitch (specifically for the SK160 models).
Leads: 12.
Enclosure Rating: IP23 - IC01.
Quality & Performance Standards: Fully compliant with EN 60034-1, IEC 60034-1, and ISO 8528-3.
Electromagnetic Compatibility: Meets EN 61000-6-2 and EN 61000-6-4 testing standards.
Performance Range Overview
The three-phase SK 160 line covers a broad spectrum of power requirements to guarantee stable electrical output for your generator sets. The capacities range from a reliable 10.1 kVA (Class F, model SK 160 SA) all the way up to a robust 49 kVA (Class H, model SK 160 WB). All models in this lineup maintain high operational efficiencies, peaking up to 88.7% for the largest configurations under load
8 weeks delivery
Technical Specifications
ELECTRICAL PERFORMANCES
| model | kVA (S1) F class 40/105°C 480V 60 Hz | kVA (S1) H class 40/125°C 480V 60 Hz | efficiency 4/4 F class p.f. 0,8 60 Hz | efficiency 4/4 H class p.f. 0,8 60 Hz |
| SK 160 SA | 10.1 | 11 | 79.4 | 79.3 |
| SK 160 CA | 12.8 | 14 | 81.9 | 81.8 |
| SK 160 CB | 16 | 17.5 | 84.4 | 84.3 |
| SK 160 MA | 20.2 | 22 | 85.6 | 85.5 |
| SK 160 MB | 22.3 | 25 | 87.3 | 87.2 |
| SK 160 LA | 27.5 | 30 | 88.1 | 88 |
| SK 160 LB | 34.8 | 36 | 88.3 | 88.2 |
| SK 160 WA | 42.2 | 43 | 88.5 | 88.4 |
| SK 160 WB | 44.9 | 49 | 88.7 | 88.6 |
Dimensions:
| model | F mm |
L mm |
W mm |
H mm |
mass SAE KG (approx) |
| SK 160 SA | 160 | 258 | 295 | 335 | 62 |
| SK 160 CA | 160 | 303 | 295 | 335 | 73 |
| SK 160 CB | 160 | 303 | 295 | 335 | 80 |
| SK 160 MA | 160 | 348 | 295 | 335 | 89 |
| SK 160 MB | 160 | 348 | 295 | 335 | 99 |
| SK 160 LA | 160 | 415 | 295 | 335 | 103 |
| SK 160 LB | 160 | 415 | 295 | 335 | 118 |
| SK 160 WA | 160 | 516 | 254 | 376 | 125 |
| SK 160 WB | 160 | 516 | 254 | 376 | 136 |